ANALYSIS OF THE INFLUENCE OF LOAD BALANCE IN THE EFFICIENCY OF 100 kVA DISTRIBUTION TRANSFORMERS IN PT. PLN (PERSERO) AIMAS UNIT

Main Article Content

john ohoiwutun
Markus Dwiyanto Tobi
https://orcid.org/0000-0002-0968-2883

Abstract

The increasing population development in Sorong district is seen from the mushrooming of developers who build housing and the construction of shops which of course the need for electrical energy continues to increase. Thus electricity is an important requirement in human life so as to obtain electricity reliably and continuously, PLN is required to manage to maintain a stable distribution of electrical energy that is sustainable to consumers. One phenomenon that is always experienced in the field is the uneven distribution of loads from the secondary side of the transformer to the customer. This causes unbalanced load between phase R, S and T which in turn causes the current to flow in the neutral conductor of the transformer, so that the current causes losses in the transformer. In this study an analysis was conducted to find out how much influence the load losses have on the efficiency of the 100 kVA distribution transformer at PLN. After calculating and analyzing, it is found that due to load imbalance in R, S and T phases, this results in daytime load losses of 0.499 kW and increases at night by 0.746 kW. Increasing load losses results in lower transformer performance and lower efficiency.

Downloads

Download data is not yet available.

Article Details

How to Cite
ohoiwutun, john, & Tobi, M. (2019). ANALYSIS OF THE INFLUENCE OF LOAD BALANCE IN THE EFFICIENCY OF 100 kVA DISTRIBUTION TRANSFORMERS IN PT. PLN (PERSERO) AIMAS UNIT. Electro Luceat, 5(2), 62-70. https://doi.org/10.32531/jelekn.v5i2.156
Section
Articles
Author Biographies

john ohoiwutun, Politeknik Katolik Saint Paul

Dosen Peneliti Prodi Diploma IV Teknik Elektro Politeknik Katolik Saint Paul Sorong

Markus Dwiyanto Tobi, Politeknik Saint Paul Sorong

Dosen Peneliti Jurusan Teknik Elektro Politeknik Saint Paul Sorong

References

[1] Bimbhra, P.S., 2011, Electrical Machinery Theory, Performance And Applications 7th Edition, Publisher: Khanna Publishers, ISBN: 9788174091734, 8174091734.
[2] Bina Tavakoli, Kashef A, 2011, Three-phase unbalance of distribution systems: Complementary analysis and experimental case study, International Journal of Electrical Power & Energy System.Chapman Stephen, 2011.
[3] Electric Machinery Fundamentals 5th (fifth) Edition, McGraw-Hill, a business unit of The McGraw-Hill Companies, ISBN 978-0-07-352954-7.
[4] Mappa, Alimuddin. 2017. “ANALISA KERJA RECLOSER UNTUK MEMPROTEKSI JARINGAN DISTRIBUSI DI PT. PLN (PERSERO) AREA SORONG”. Electro Luceat 3 (1), 5-9. https://doi.org/10.32531/jelekn.v3i1.26.
[5] ohoiwutun, john. 2017. “Analisa Rugi Daya Transformator 100 KVA Gardu Rufei Pantai Di PT.PLN (Persero) Area Sor”. Electro Luceat 3 (1), 24-31. https://doi.org/10.32531/jelekn.v3i1.33.
[6] Tobi, Markus. 2018. “ANALISIS PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN LOSSES PADA TRANSFORMATOR DISTRIBUSI DI PT PLN (PERSERO) AREA SORONG”. Electro Luceat 4 (1), 5-14. https://doi.org/10.32531/jelekn.v4i1.80.
[7] Tobi, Markus, and VINA VAN HARLING. 2017. “PENGARUH OPTIMASI TRANSFORMATOR DAYA TERHADAP PERKEMBANGAN BEBAN FEEDER UNTUK MEMINIMALISASI GANGGUAN DAN DEFISIT BEBAN LISTRIK DI WILAYAH SORONG-PROVINSI PAPUA BARAT”. Electro Luceat 3 (1), 10-18. https://doi.org/10.32531/jelekn.v3i1.28.
Abstract viewed = 304 times
PDF downloaded = 756 times